Direct Digital Controls (DDC)
Installation, Operation, and Maintenance Manual
Save these instructions
. This document is the property of the owner of this equipment and is required
for future maintenance. Leave this document with the owner when installation or service is complete.
RECEIVING AND INSPECTION
Upon receiving unit, check for any interior and exterior damage, and if found, report it
immediately to the carrier. Also check that all accessory items are accounted for and are
damage free.
INSTALLATION & PROGRAMMING WARNING!!
Direct Digital Controls should only be set up by trained Controls Contractors or similarly
trained personnel. For proper operation, a thorough understanding of the total system design
is required. If you are unsure of the proper setup and operation of this unit, please contact
your onsite Controls Contractor.
Przeglądanie stron 0
1 2 3 4 5 6 ... 19 20

Podsumowanie treści

Strona 1 - May 2014 Rev. 3

A0020659 May 2014 Rev. 3 Direct Digital Controls (DDC) Installation, Operation, and Maintenance Manual Save these instructions. This

Strona 2 - TABLE OF CONTENTS

10 AV: 12: Heating Valve Output. This is the output, in percentage, of the PID loop which feeds the heating valve. A value of 0% is low fire, an

Strona 3 - WARRANTY

11 AV: 16: Modulating Damper Output. This is the output, in volts (V), which is being sent to the modulating damper from the controller. This AV

Strona 4 - INSTALLATION

12AV: 20: Space (Room) Air Temperature Sensor. This variable provides the room air temperature sensor reading from the field installed sensor. Pro

Strona 5

13LIST OF BINARY VARIABLES (BV): BV: 1: BV Unit Enable (BAS). This is the Unoccupied/Occupied switch used for BAS control of unit run condition.

Strona 6

14 BV: 6: Outside Air Damper Command. This is the command to control the on/off state of the outside air damper. Used to confirm if the unit is

Strona 7

15 BV: 11: 2nd Stage Cooling Command. This is the command used to activate the stage 2 cooling output from the controller. Properties - F

Strona 8

16BV: 16: Room Override Status. This is the status of the room override space heating function. . Room Override will be On if the unit is operati

Strona 9

17- Activates if AV: 9, the Discharge Air Temperature, is greater than AV: 7, the cooling setpoint, plus 5.0 degrees, for 5 minutes. Cooling must b

Strona 10

18- Network Reference: oad_rntm - Modbus Register: 10023 - N2 Register: 23 - Lonworks ID: nvoOadRntmAlm - Activates if BV: 7 has been in the On

Strona 11

19LOGIC MODIFICATION NOTES AV:1 AV:2 AV:3 AV:4 AV:5 AV:6 AV:7 AV:8 AV:9 AV:10 AV:11 AV:12 AV:13 AV:14 AV:15 AV:16 AV:17 AV:18 AV:19 AV:20 AV:21 AV:2

Strona 12

2 TABLE OF CONTENTS WARRANTY ...

Strona 13

20Start-Up and Maintenance Documentation Job Information Job Name Service Company Address Address City City State State Z

Strona 14

3WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months f

Strona 15

4INSTALLATION It is imperative that this unit is installed and operated with the designed airflow and electrical supply in accordance with this ma

Strona 16 - NETWORK ALARM VARIABLES

5DDC PROTOCOL SELECTION 1. The appropriate DDC controls protocol is factory set using dip switches on the DDC controller. The four possible protoco

Strona 17

62. Using the rotary switches, set the controllers address. The factory default is 03. The number used is arbitrary, so long as it doesn’t conflic

Strona 18

7SOFTWARE SETUP & NETWORK VARIABLES The DDC controller provides a fixed set of analog and binary variables for adjustment in the field. These v

Strona 19 - LOGIC MODIFICATION NOTES

8 AV: 4: Effective Heating Setpoint. This is the effective heating setpoint, after the inclusion of internal logic to prevent rapid ramp-up/down

Strona 20

9 AV: 8: Cooling Stage 2 Offset. This is the offset value from AV:6, which will activate the second stage cooling. If the Intake Air Temperature